Smoke Detectors |
|
|
NS Series Photoelectric Smoke
Detector |
|
The
SLR-24 can be used in all areas where Photoelectric
Smoke Detectors are required. The wide range smoke
chamber makes the SLR-24 well suited for a wide
variety of applications ranging from smoldering to
flaming type fires. |
 |
SLR-24 -
Photoelectric Smoke Detector Head
Rated Voltage - 17.7-30.0 VDC,
Working Voltage 15.0 - 33 VDC, Maximum Voltage 42
VDC, Supervisory Current 45uA @ 24 VDC, Surge
Current 160uA Max. @ 24 VDC, Alarm Current 150MA
max. @ 24 VDC, Ambient Temperature 32°F to 120°F
(0°C to 49°C) |
|
SLR-24H -
Combination Heat / Photoelectric Smoke Detector Head
Rated Voltage - 17.7-30.0 VDC,
Working Voltage 15.0 - 33 VDC, Maximum Voltage 42
VDC, Supervisory Current 45uA @ 24 VDC, Surge
Current 160uA Max. @ 24 VDC, Alarm Current 150MA
max. @ 24 VDC, Ambient Temperature 32°F to 120°F
(0°C to 49°C)
Self Restoring Heat Detector Rated at 135°F (57°C) |
|
|
NS Series Smoke Detector
Base |
 |
NS6-220 -
Smoke Detector Base For SLR Series
Detectors
Compatible with the SLR-24 and SLR-24H model
smoke detectors.
Click
here
for detail. Use your browsers back to
return to this page. |
|
|
Manuals and Reference Guides |
|
Description |
File Name |
Format |
Size |
|
NS-Series SLR-24
Photoelectric Smoke Detector Product Data Sheet |
ds-8559.pdf |

PDF File |
79k |
|
 |
|