Comparison of Linear Heat Detection Technologies

Linear Heat Detector Comparison Chart

Feature Protectowire Digital Analog Integrating (1) Continuous
Thermocouple (1)
Maximum Zone Length Up to 5,000 FT. (1,524 m) 1,500 FT. (457.2m) 2,000 FT. (609.6m)
Alarm Point Location YES NO NO
Multiple Alarm Points Within Zone YES NO NO
Underwriters Laboratory (UL) Listed YES NO NO
Factory Mutual (FM) Approved YES YES NO
Alarm Point Setting  Unaffected by Changes in Ambient Temperature YES NO YES
Compatible with Standard Initiating Devices (Manual Stations, Contact Devices and Smoke Detectors) YES NO NO
Pre-Alarm Capability YES YES YES
Approved for use in Hazardous Locations YES YES ? *
Easy to Splice / Terminate YES NO ? *
Maximum Alarm Temperature 356°F (180°C) 500°F (260°C) 350°F (177°C)
Expected Service Life Current Installations Greater than 20 Years ? * ? *
Requires On Site Calibration NO YES NO
Size 5/32 in. (4 mm) 0.09 in. (2.28 mm) 1/8 in. (3.175 mm)
Annual Maintenance per NFPA 72, 1999 Minimal Heat Test - Must alarm within 1 minute ? *
Accuracy dependent on length NO YES NO
Designed and Manufactured by and ISO-9001 Registered Company YES ? * ? *
Feature Protectowire Digital Analog Integrating (1) Continuous
Thermocouple (1)
(1) - Based on available information at the time of publication 4/13/01
? * - Information unknown or not available

 