Conventional Heat Detectors


5600 Series Heat Detectors
(Replaces 600 Series)

The 5600 Series Heat Detector is a durable, low profile unit which protrudes only 1.7 inch (4.3cm) from the mounting surface when mounted on a recessed junction box. It is available in combination rate-of-rise and fixed temperature models with temperature ratings of 135°F (57°C) or 194°F (90°C). Each 5600 Series Detector includes a reversible mounting plate which attaches to a 4 inch junction box, 3.50 inch octagonal box, or plaster ring. When reversed, the plate can be used for open wiring without a junction box. Electrical Rating 6-28 VDC, 1 amp. (all models).  Refer to product data sheet for FM approval and spacing information.


Photo Depicts 5600 series detector. All units similar in packaging

5601P - Low Profile, Rate of Rise and Fixed Temperature 135°F Maximum Spacing - UL 50' x 50' (15.2m x 15.2m)

5602 - Low Profile, Rate of Rise and Fixed Temperature 194°F Maximum Spacing - UL 50' x 50' (15.2m x 15.2m)

5603 - Low Profile, Fixed Temperature 135°F Maximum Spacing - UL 25' x 25' (7.6m x 7.6m)

5604 - Low Profile, Fixed Temperature 194°F Maximum Spacing - UL 25' x 25' (7.6m x 7.6m)


Rate Anticipation Heat Detectors

All 302 Series Detectors are normally open devices and are available in either 135°F (57°C) or 194°F (90°C) ratings. Each unit is constructed with a high expansion .040 anodized aluminum sensing shell and fine silver contacts which are hermetically sealed to ensure reliable operation. Electrical Rating 6-28 VDC, 1 amp. (all models).  Refer to product data sheet for FM approval and spacing information.

302-135- Interior, Vertical Mounting Fixed Temperature 135°F Maximum Spacing - UL 50' x 50'

302-194 - Interior, Vertical Mounting Fixed Temperature 194°F Maximum Spacing - UL 50' x 50'

302-ET-135 - All Weather, Vertical Mounting Fixed Temperature 135°F Maximum Spacing - UL 50' x 50'

302-All Weather, Vertical Mounting Fixed Temperature 194°F Maximum Spacing - UL 50' x 50'

302-AW-135 - Moisture and Dust Proof, Vertical Mounting Fixed Temperature 135°F Maximum Spacing - UL 50' x 50'

302-AW-194 - Moisture and Dust Proof, Vertical Mounting Fixed Temperature 194°F Maximum Spacing - UL 50' x 50'

302-EPM-135 - Explosion Proof Screw Base, Vertical Mounting Fixed Temperature 135°F Maximum Spacing - UL 40' x 40'

302-EPM-194Explosion Proof Screw Base, Vertical Mounting Fixed Temperature 194°F Maximum Spacing - UL 40' x 40'

AP-P - Adapter Plate for 4" Box, used with 302, 302-H and 302-AW


 